Modern Packaged Boiler Operation, Maintenance and Training

Modern Packaged Boiler Operation, Maintenance and Training

The latter area of the 20th Century saw the introduction of more stringent boiler manufacturing standards, particularly with regards to welding technology and inspection, and the evolution of digital control systems that now offer an unsurpassed degree of reliability. The present day, micro-processor based, high-integrity, "Boiler Control System" (BCS) has the capacity to perform lots of the tasks traditionally undertaken by the qualified operator allowing extended periods of automatic operation without the human intervention whatsoever. An integral feature of modern packaged boilers is that they are created to operate unsupervised for extended periods.

The amount of human supervision and operator training requirements are determined by the level of sophistication of the "Boiler Control System" (BCS). They are defined in local boiler codes and standards and differ widely between jurisdictions. For example, in a few, a high-pressure boiler is defined as any boiler operating above 1 BAR (approximately 15 psig) pressure and, no matter all the considerations, it must all the time be beneath the control of an appropriately qualified operator. Other jurisdictions impose capacity constraints on unsupervised operation however in many, boiler codes and other relevant legislation have been revised and extended to accommodate the demand from industry because of this type of boiler.

Industrial boilers of most types generally fall into among three categories in terms of their operational and qualification requirements. They're:

? Attended Boilers;
? Limited-Attendance Boilers;
? Unattended Boilers.

What is a "packaged boiler"?

The term "Packaged Boiler" can be used to spell it out a boiler that is factory built and delivered either fully assembled or, as pre-built modules which might be easily assembled on site. It really is essentially a self contained unit complete with a control system and all equipment required for operation. The boiler manufacturer assumes responsibility for several components and after delivery all that is required is for it to be connected to the steam distribution system, water, fuel, and electricity supplies. Virtually all small and mid-sized boilers manufactured today are packaged boilers plus they may be the conventional firetube or watertube type, including their derivatives or, hybrid boilers such as for example once-through coil and electrode boilers.

What's an attended boiler?

Until relatively recently, almost all steam boilers operated in the "Attended" mode. That's, they were necessary to have an appropriately qualified operator on-site and in the immediate vicinity of the boiler at all times that it was operating. Because the introduction of micro-processor based technology to boilers from around 1990 onwards, many traditional attended boiler owners have upgraded their control systems. Given also that micro-processor based controls are now an almost universal feature on new packaged-boilers, the original boiler attendant is becoming an endangered species in small to mid-sized plants supplying process steam. At the minimum, their role has changed from that of direct, hands-on operation to 1 of supervising the operation of the BCS and performing tasks that ensure its continuing integrity and compliance with the requirements of boiler codes and standards.

Boiler operation has evolved to the point that in lots of jurisdictions, fully attended operation is unusual outside of large, complex plants. The exceptions are large power utilities, chemical recovery boilers and similar integrated processes where in fact the boiler is really a key component.

exactly what is a limited-attendance boiler?

The Limited-Attendance mode of operation allows for periodic checking of the boiler at set minimum intervals instead of continuous attendance. An integral feature of limited-attendance boilers is that they may anytime be brought under the control of an appropriately qualified operator and operated in the fully attended mode under continuous supervision.

Many older packaged boilers and the ones which have been upgraded from attended status are classified as limited-attendance due to the fact their control systems do not achieve exactly the same standards of integrity and reliability as do modern micro-processor based systems. Many likewise incorporate provision for manual intervention which generally in most jurisdictions disqualifies them for consideration for unattended status.

What is an unattended boiler?

An Unattended Boiler is actually a fully automatic boiler that operates under the continuous supervision and control of a complicated, micro-processor based, BCS. The BCS controls the complete boiler function like the energy input management system (on oil and gas-fired boilers commonly known as the "Burner Management System" or, BMS), the water level management system, the security alarm, the pressure controls, trip devices, all instruments and circuitry.

A key feature of this kind of boiler is that in most jurisdictions boiler codes and standards dictate a boiler that is classified as unattended must be under the continuous supervision and control of the BCS all the time that it is in service. The unattended boiler may only be operated in unattended mode. It may not be operated in attended mode under any circumstances even for brief periods and also if a qualified operator is available. Used, the BCS employed on an unattended boiler does not have any provision for manual operation. In case of a control system fault or a potentially unsafe condition, the BCS will shut down the boiler and lock-out the energy input system. It will prevent a boiler restart until such time that the control system fault has been repaired or, the potentially unsafe condition has been addressed and every one of the BCS inputs indicate that the boiler is in a safe condition.

The BCS is equipped with some method of recording all major events that cause the alarms to activate. On early unattended boilers this was typically a simple printer that recorded such events on a line-by-line basis. More modern systems however, store the info in the onboard micro-processor memory for an extended period. They typically record a much wider selection of information to supply improved oversight of boiler performance and, are sometimes integrated with a plant-wide information system which facilitates the remote storage of data for extended periods.

The unattended boiler is really a relatively recent phenomenon. Traditionally most boiler installations operated beneath the continuous supervision of a professional operator although in lots of jurisdictions, some small boilers were permitted to operate in limited-attendance mode. Until very recently, generally in most jurisdictions unattended boiler operation was at the mercy of strict constraints. Typically, permissible maximum operating pressure and design output were severely limited and in many locations those constraints still apply, at least on paper. Recently however, boiler codes and standards in lots of jurisdictions have been extended to accommodate this sort of boiler and in others it is becoming quite common for local regulatory authorities to grant exemptions on a case-by-case basis.

With the advent in recent years of improved manufacturing standards and the rapid evolution of sophisticated, increasingly reliable micro-processor based control and monitoring systems, most small to medium sized packaged boilers from reputable manufacturers now incorporate a high-integrity BCS as standard equipment. Where unattended operation is permitted, they may only require inspection and operational certification by an accredited inspection body to make sure compliance with National and local standards.

Limited-Attendance vs Unattended Operation

To achieve Limited-Attendance or Unattended classification, the boiler is at the mercy of strict statutory oversight covering operation, maintenance, servicing and record keeping. Boiler codes and standards require that boilers in either category be built with a minimum, specified inventory of safety equipment that may automatically shut down the boiler in the event of a potentially unsafe condition.

The classification applied to a specific packaged boiler depends largely on the sophistication of the BCS or, sometimes, the kind of fuel that is fired. For instance, a 10 MW boiler firing gas may achieve unattended classification in which a similar 10 MW boiler from exactly the same manufacturer but firing solid-fuel may be classified as limited-attendance. Firing solid-fuels, particularly people that have a variable moisture content, is sometimes something of a black-art requiring a degree of skill and experience. In this author's jurisdiction, unattended solid-fuel boilers are nevertheless not uncommon even for quite large boilers over 20 MW capacity and often in multiple boiler installations.

The key differences between the Limited-Attendance and Unattended modes of operation are:

Limited Attendance

? An appropriately qualified operator or responsible person must be on-site at all times that the boiler is operating;

? Codes and standards usually require that the boiler be continuously supervised during startup and shutdown periods;

? During normal operation, the limited-attendance mode allows for periodic checking of the boiler at set minimum intervals rather than continuous supervision;



? Limited-Attendance boilers may anytime be brought beneath the control of an appropriately qualified operator and operated in the fully attended mode under continuous supervision;

? The operator or responsible person should be on-site at all times that the boiler is operating and should be immediately available if required.

Unattended

? Where unattended operation is permitted, a professional operator is not a mandatory requirement. The boiler may be supervised by an appropriately trained "Responsible Person";

? The operator or responsible person may leave the website provided that he or she is available to respond to boiler outages. That is usually attained by a pager or cellphone signal transmitted by the BCS;

? In many jurisdictions, unattended boilers may begin up and turn off automatically under the control of the BCS provided that they are suitably equipped to the satisfaction of an approved inspection body;

? Unattended boilers are permitted to operate unsupervised for extended periods and in most jurisdictions that is currently 24-hours. Recent control and monitoring systems innovations by some manufacturers however, have seen that period extended in some jurisdictions. The 72H notation in Europe for example, signifies that the boiler is approved for unsupervised operation for periods as high as 72-hours;

? Boiler codes generally in most jurisdictions specifically forbid the provision for manual intervention in the operation of unattended boilers. They must always be beneath the control of the BCS. That's, they may only be operated in unattended mode. They may not be operated in attended mode under any circumstances even for brief periods and also if a qualified operator can be acquired.

Training Requirements

Boilers which are certified for unattended operation do not need a qualified operator. This relaxation of the manning requirements imposes substantial obligations on boiler owners, controllers, manufacturers and inspection bodies to make sure compliance with boiler codes and other relevant legislation and, that boiler supervisory and maintenance staff receive adequate training. Non compliance will almost always be interpreted as a breach of Occupational Safety and Health legislation that may result in severe penalties particularly if the non compliance is discovered because of an incident or accident.

Accident investigation reports demonstrate that the most common contributing causes to boiler accidents are operator intervention with the safety controls, inadequate maintenance, device failure following maintenance by unqualified personnel, isolation or deliberate disablement of the safety devices, inappropriate operating practices and inadequate water treatment. Automatic controls aren't a complete replacement for supervision. A way of measuring supervision by a qualified operator or perhaps a trained Responsible Person familiar with the BCS and the operation of the boiler plant can be an essential feature of safe operation.

Unattended boilers that are operated in strict compliance with the manufacturer's recommendations, boiler codes and standards have a fantastic safety record worldwide. Because they're designed to operate unsupervised for extended periods, routine operating, maintenance and inspection requirements are generally more stringent than for other styles of boilers.  Middlesbrough Boiler Service  and its associated safety devices clearly play a key role in the safe operation of this type of boiler and are therefore subject to strict compliance with routine testing procedures by the trained Responsible Person and the approved maintenance contractor. It is very important that there should be a high degree of confidence in the integrity of the BCS and the routine testing procedures should therefore be regarded as a key element of safe operation.

Although those tests are usually universal in nature, there are differences in their implementation between jurisdictions. It is therefore essential that the boiler owner, controller and trained Responsible Person recognize that they have a responsibility to familiarise themselves with the local codes and regulations applying to this type of boiler. Failure to meet up that obligation will usually be interpreted as a breach of OSHA regulations. If in doubt, you need to seek clarification from your boiler inspector, inspection body, the boiler manufacturer or the neighborhood regulatory authority.

Who's the boiler controller? - roles and responsibilities:

Boiler codes and standards generally require that unattended boiler installations have a nominated "Controller". This can be the owner or, a person nominated by the dog owner to perform that role. The Controller will not necessarily need to be closely involved with hands-on, day-to-day operation but instead, to supply general oversight of the boiler operation and maintenance.

The Controller's responsibilities include:

? Ensuring compliance with the Boiler code or relevant standard including the maintenance of appropriate operational and engineering records;

? Ensuring that the boiler is supervised by appropriately qualified or trained persons;

? The implementation and maintenance of a Quality Management System (QMS);

? The implementation and maintenance of appropriate safety and environmental procedures and, communications with the correct regulatory bodies for instance, OSHA, environmental agencies, inspection bodies and so on.

The Controller is normally a engineering, maintenance or departmental manager or, someone in the organization that holds a qualification or Certificate of Competency in boiler operation.

exactly what is a trained responsible person? - roles and responsibilities:

A "Trained Responsible Person" is somebody who is appointed by the controller to exercise day-to-day supervision of the boiler. They're not required to hold a formal qualification such as a certificate of competency but, must be trained to an even specified by the boiler manufacturer or, to an even acceptable by an inspection body or other appropriate regulatory authority. The Responsible Person is not required to have an intimate knowledge of boiler technology but instead, a basic level of knowledge and an understanding of the functionality and roles of the boiler components, mountings and ancillary systems like the fuel, feedwater, and steam distribution systems.

The principal roles of the Responsible Person are to exercise general day-to-day supervision of the boiler operation, verify that all control and alarm systems are functioning correctly also to ensure compliance with the routine testing procedures specified in the relevant code or standard and, by the boiler manufacturer. The Responsible Person should not necessarily be likely to diagnose and rectify equipment or system failure. They must be competent to respond to alarms, and to take appropriate action which, at the very least, means that the boiler is shut down safely before calling for assistance.

what's an approved maintenance contractor?:

Compliance with defined maintenance procedures is a key facet of unattended boiler operation. There were a variety of recent catastrophic boiler incidents resulting from inappropriately performed maintenance tasks which in some cases, were undertaken by qualified and experienced tradesmen but, who lacked the expert understanding requirements associated with boiler maintenance.

The "Approved Maintenance Contractor" is a person or organisation with the correct skills, knowledge and experience to keep up the boiler and its own components to a standard acceptable by the product manufacturer and the inspection body. They need to have a thorough understanding of the role and functionality of the BCS in relation to limited-attendance and unattended operation.

Boiler codes and regulations define minimum acceptable standards because of this role which might differ between jurisdictions. Generally, they will require that the nominated organisation be considered a boiler manufacturer or an unbiased contractor approved by the manufacturer or the inspection body. In organisations which have their own internal maintenance infrastructure, the Controller may apply to the inspection body to nominate the business itself as the approved maintenance entity. In such cases, the organisation must fulfill the requirement that nominated personnel performing the task have appropriate training and experience. Which will typically require that nominated workers can provide evidence of an appropriate trade qualification or, have obtained specialist training and also have sufficient experience. Under no circumstances whatsoever should non-approved staff be permitted to perform maintenance on any pressure equipment or the BCS and its own field devices including all safety devices and the power input system.